     F-1100 Single Turbine Insertion Flow Meter - suitable for measuring flow in HVAC and process piping systems. This model provides a high-resolution frequency output for connection to an ONICON Display or BTU meter. 4-20 Ma and 0-10 VDC are standard outputs.

    Accuracy - ±0.5% of reading at calibrated velocity, ±1% of reading from 3-30 ft/s, 2% of reading from .04 -3 ft/s 

    System-1 BTU Meter Model 100 single mode heating or cooling - provides highly accurate thermal energy measurement based on signal inputs from two matched temperature sensors (included) and any of ONICON's insertion or inline flow meters (ordered separately).  The Model 100 is designed for single mode applications (heating or cooling).

    Accuracy - Differential temperature accuracy ±0.15° F over calibrated range. Computing nonlinearity within ±0.05%.